ATEX / EEx equipment service process map
A swimlane map of servicing hazardous-area electrical equipment from a service request to return to operation, across ServiceDesk, Field Electrical, an ATEX/EEx Specialist, QA/Compliance and the Customer. The map holds the job rather than proceeding the moment certification can't be confirmed.
Opens a copy in the editor and saves it in this browser. No account, nothing sent anywhere.
What is in this map
15 steps across 5 swimlanes and 5 phases, with 2 decision points.
- Swimlanes (who does the work)
- ServiceDesk, Field Electrical, ATEX / EEx Specialist, QA / Compliance and Customer
- Phases (left to right)
- Identification & certification, Isolation & inspection, Service / repair, Compliance & testing and Documentation & return
Why map this process
Explosion-protected equipment is only as safe as its certification matches its as-found condition, and this map's first real decision enforces that literally: a nameplate marking, protection type, gas or dust group and temperature class that can't be confirmed against the equipment routes to a HALT row, not a visual best guess. The halt row's own comment is careful to say the job is held, not written off — service resumes once the gap is actually resolved, with certification re-verified from scratch rather than assumed fixed.
The enclosure-compliance decision near the end carries the same weight in the other direction: it checks flamepath gaps, gasket condition and fastener torque against the manufacturer's actual tolerances, because the comment states plainly that a missing gasket or an under-torqued fastener defeats the protection exactly as surely as an uncertified nameplate does. Two different failure modes, same consequence, and the map gives each one its own gate rather than one general 'inspection passed' box.
Every step in the map
This is the spreadsheet behind the diagram. The numbers in “Goes to” are row numbers, which is exactly what the editor’s “Line to” column holds — so you can read the flow here and retype any part of it.
| # | Step | Shape | Swimlane | Phase | Goes to |
|---|---|---|---|---|---|
| 1 | EEx equipment service request received | Start | ServiceDesk | Identification & certification | 2 |
| 2 | Identify hazardous-area equipment and zone classification | Process | ATEX / EEx Specialist | Identification & certification | 3 |
| 3 | Verify ATEX/EEx certification against nameplate and zone | Process | ATEX / EEx Specialist | Identification & certification | 4 |
| 4 | ATEX/EEx certification **current** and matches equipment? | Decision | ATEX / EEx Specialist | Identification & certification | 6 (Certification confirmed), 5 (Certification missing or invalid) |
| 5 | **Halt** job, request missing certification or documentation | Blocked | ServiceDesk | Identification & certification | 3 |
| 6 | Isolate equipment and apply *lock-out/tag-out* | Process | Field Electrical | Isolation & inspection | 7 |
| 7 | Inspect enclosure, flamepaths, gaskets and cable entries | Process | ATEX / EEx Specialist | Isolation & inspection | 8 |
| 8 | Service or repair EEx equipment | Process | Field Electrical | Service / repair | 9 |
| 9 | Enclosure restored to **EEx compliance** (gaskets, torque, flamepath gaps)? | Decision | ATEX / EEx Specialist | Compliance & testing | 11 (Compliant), 10 (Non-conforming) |
| 10 | Rework enclosure closure to correct non-conformance | Process | Field Electrical | Compliance & testing | 9 |
| 11 | Functional and insulation testing | Process | QA / Compliance | Compliance & testing | 12 |
| 12 | Complete EEx service documentation and **compliance certificate** | Document | ATEX / EEx Specialist | Documentation & return | 13 |
| 13 | Customer review and sign-off on compliance certificate | Approval | Customer | Documentation & return | 14 |
| 14 | De-isolate and return equipment to operation | Process | Field Electrical | Documentation & return | 15 |
| 15 | Equipment back in service, EEx compliance certificate issued | End | Field Electrical | Documentation & return | End |
The decision points
Every branch in the map, with the label on each outgoing line. These are the questions the process has to be able to answer.
-
4. ATEX/EEx certification **current** and matches equipment?
Owned by ATEX / EEx Specialist · Identification & certification
- Certification confirmed → step 6
- Certification missing or invalid → step 5
-
9. Enclosure restored to **EEx compliance** (gaskets, torque, flamepath gaps)?
Owned by ATEX / EEx Specialist · Compliance & testing
- Compliant → step 11
- Non-conforming → step 10
Notes on specific steps
These notes travel with the map. In the editor they live in the Notes column and appear when you open a box.
- 1. EEx equipment service request received
- Customer reports a fault or requests scheduled service on equipment already installed and certified in a classified hazardous area. The zone and the equipment's as-installed certification are confirmed before anything downstream is scheduled.
- 4. ATEX/EEx certification **current** and matches equipment?
- Current means the nameplate ATEX/IECEx marking, protection type, gas or dust group and temperature class still match the equipment's as-found condition, and any prior modification is documented. A marking that cannot be confirmed against the equipment routes to Halt rather than a visual best guess.
- 5. **Halt** job, request missing certification or documentation
- The job is held, not written off. Service resumes once the manufacturer's declaration of conformity, a replacement nameplate record, or the customer's own equipment file resolves the gap, and certification is verified again from scratch.
- 7. Inspect enclosure, flamepaths, gaskets and cable entries
- Photographed and measured before the enclosure is disturbed further, so the as-found flamepath gaps, gasket condition and cable entry seals are on record if a defect surfaces later in the job.
- 9. Enclosure restored to **EEx compliance** (gaskets, torque, flamepath gaps)?
- Checked against the manufacturer's flamepath gap tolerance, gasket condition and the specified fastener torque values, not a general close-up look. A missing gasket, an under-torqued fastener or a flamepath gap outside tolerance defeats the protection exactly as surely as an uncertified nameplate does.
Making it yours
Phases (Identification & certification, Isolation & inspection, Service/repair, Compliance & testing, Documentation & return) run Horizontal lane; the five roles, with ATEX/EEx Specialist as its own lane distinct from Field Electrical, run Vertical lane. When you adapt the certification-verification row, keep its Notes naming the exact document set you accept as proof (manufacturer's declaration of conformity, a replacement nameplate record, the customer's own equipment file) — that's the list the halt row's loop actually resolves against.
What to watch out for
- Don't skip photographing and measuring the as-found enclosure condition before disturbing it further. The inspect-enclosure row's comment is specific about why: if a defect surfaces later in the job, the as-found flamepath gaps, gasket condition and cable-entry seals need to already be on record, not reconstructed from memory.
- Keep the compliance decision's tolerance checks (flamepath gap, gasket, torque) as named items rather than a single 'looks fine' pass. The row's own comment lists them because each is a distinct way the protection rating gets defeated, and a generic close-up look catches fewer of them than a checklist against the manufacturer's actual figures.
- Don't return equipment to operation before the compliance certificate has the customer's own sign-off. The map places customer review before de-isolation for a reason: the customer's compliance obligation for that equipment doesn't transfer back to them silently just because the job is considered finished.
Frequently asked questions
What actually triggers the 'certification missing or invalid' branch?
Any mismatch the specialist can't resolve on the spot between the nameplate's ATEX/IECEx marking and the equipment's as-found condition — an illegible or damaged nameplate, an undocumented prior modification, or a protection type that doesn't match what the zone requires. The row halts rather than guesses, because a guess here is the one that defeats hazardous-area protection silently.
Is 'service or repair' the same regardless of what's wrong with the equipment?
No — it's drawn as one row because the compliance gate afterward applies identically to any service or repair, but the actual work varies from a gasket replacement to a full internal rebuild. Add the specifics as Notes rather than splitting the row; the gate that matters is the one that follows, not the repair method itself.
Why does functional testing come after the compliance decision rather than before?
Because compliance (the physical protection — flamepaths, gaskets, torque) has to be confirmed before the enclosure is considered safely closed, and functional testing (does the equipment actually work) is only meaningful once you know the enclosure protecting it is sound. Testing a unit that hasn't cleared compliance risks masking a protection defect behind a working function test.